Newtec Power Machinery Co.,Ltd
|
Price: | 10000.0~20000.0 USD |
Payment Terms: | T/T,L/C,D/A,D/P |
Place of Origin: | Jiangsu, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Technical data | |
Genset Model | NTV-100GF |
Prime Power | 100kw/125kva |
Rated Voltage | 400/230V |
Frequency | 50/60Hz |
Power Factor | 0.8(lagging) |
The regulating rate of steady voltage | ≤±0.5% |
The regulating rate of instantaneous voltage | ≤-15%/ +20% |
The time of steady voltage | ≤1.5sec |
The waving rate of voltage | ≤1.0% |
The regulating rate of steady frequency | ≤3% |
The regulating rate of instantaneous frequency | ≤±10% |
The time of steady frequency | 3sec |
Dimension (L×W×H) (mm) | 2200*1000*1450 |
Genset weight (kg) | 1200 |
Diesel Engine | |
Brand | Volvo |
Mode | TAD532GE |
Number of Cylinde | 4 |
Rotating Speed | 1500/18000RPM |
Cycle | Four stroke |
Type | waste gas turbine boost,direct spurting type |
Bore×Stroke(mm) | 108*130 |
Displacement(L) | 4.76 |
Lubricating Capacity(L) | 15 |
Speed Governor | Electrical |
Cooling System | Water-cooled |
Speed Stability (%) | ≤5% |
Fuel Consumption at 100% Load | 214 g/kw.h |
Starting Method | DC24V Electrical starting |
Alternator | |
Brand | Stamford |
Model | UCD-series |
Number of Phase | 3 |
Connecting Type | Three Phase and Four Lines |
Number of Bearing | 1 |
Grading Protection | IP22 |
Altitude | ≤1000m |
Exciter Type | Brushless (AVR automatic voltage regulating) |
Insulation Class | H degree |
The components of the genset | |
(1) Volvo Penta Diesel Engine; (2)Stamford Alternator; (3) Control Panel | |
Control Panel | |
The control panel is Quadruplication protection control panel, with the display of frequency table/water temperature/schedule/battery voltmeter. The genset with low oil pressure, high water temperature, over speed emergency, stop and other pre-protection. |